Voltage
110/120 VAC or 220/230/240 VAC
Voltage Range
81-145 VAC / 162-290 VAC
Frequency Range
60/50 Hz (auto sensing)
Power Factor
0,6
Voltage
110/120 VAC or 220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
+- 10
Frequency Range
60 Hz or 50 Hz ±1 Hz
Waveform
Simulated Sinewave
Transfer time
Typical 2 -6ms
Outlets
2 x Schuko
Battery Type & Number
12 V/7 Ah x 1
Typical Recharge Time
4-6 hours recover to 90% capacity
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every second
Overload
Sounding every 0.5 second
Fault
Continuously sounding
Protections
Overload, discharge, and overcharge protection
Dimension
279 x 101 x 142
Net Weight
4.2 kg
Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 40dB
Optional USB / RS232 Port
Supports: Windows? 2000/XP/Vista/7/8/10, Linux, Unix, Mac OS

Available
Code
0.501.494
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz + - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 - 7 ms, 10 ms max.
DC voltage
12 V
Configuration
12 V / 7 Ah x 1
Recharge time
6 - 8 h
USB (optional)
Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
Short circuit - battery overcharge , overdischarge , overload - surge
Humidity
20 - 90% RH @ 0- 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 4.2 / 4.6, Dimensions 90 x 305 x 165, Packaged dimensions: 133 x 349 x 232, Quantity /20ft 2300 pcs

Available
Code
0.502.038
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 -295 Vac (145 -295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz+ - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 -7 ms, 10 ms max.
DC voltage
12 V
Configuration
12 V / 7 Ah x 1
Recharge time
6 - 8 h
USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
hort circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 -90% RH @ 0 - 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 4.2 / 4.6, Dimensions 90 Χ 305 Χ 165, Packaged dimensions: 133 x 349 x 232, Quantity /20ft 2300 pcs

Available
Code
0.502.272
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 -295 Vac (145 -295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz+ - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 -7 ms, 10 ms max.
DC voltage
12 V
Configuration
12 V / 9 Ah x 1
Recharge time
6 - 8 h
USB (optional)
Supports Windows 98 / 2000 / 2003 / XP / Vista / 2008 / Windows7 / 8 / 10
Protections
hort circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 -90% RH @ 0 - 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 5.0 / 5.4, Dimensions 90 Χ 305 Χ 165, Packaged dimensions: 133 x 349 x 232, Quantity /20ft 2300 pcs

Available
Code
0.501.495
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz + - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 - 7 ms, 10 ms max.
DC voltage
12 V
Configuration
12 V / 9 Ah x 1
Recharge time
6 - 8 h
USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
Short circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 - 90% RH @ 0- 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 5.0 / 5.4, Dimensions 90 ? 305 ? 165, Packaged dimensions: 133 x 349 x 232, Quantity /20ft 2300 pcs

Available
Code
0.502.039
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz + - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 - 7 ms, 10 ms max.
DC voltage
24 V
Configuration
12 V / 7 Ah x 2
Recharge time
6 - 8 h
USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
Short circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 - 90% RH @ 0- 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 9.4 / 9.9, Dimensions 115 x 320 x 220, Packaged dimensions: 161 x 369 x 290, Quantity /20ft 1400 pcs

Available
Code
0.500.950
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz + - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 - 7 ms, 10 ms max.
DC voltage
24 V
Configuration
12 V / 9 Ah x 2
Recharge time
6 - 8 h
USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
Short circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 - 90% RH @ 0- 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Plastic Case
Net / Gross weight (kg) 9.8 / 10.3, Dimensions 115 x 320 x 220, Packaged dimensions: 161 x 369 x 290, Quantity /20ft 1400 pcs

Available
Code
0.500.869
Category
Tescom UPS
Voltage
100 / 110 / 120 V: 80 - 150 Vac, 220 / 230 / 240 V: 162 - 295 Vac (145 - 295 Vac optional)
Frequency
50 / 60 Hz + - 10% (auto-sensing)
Voltage
100 / 110 / 120 Vac + - 10% or 220 / 230 / 240 Vac + - 10%
Frequency
50 / 60 Hz + - 1% (auto-sensing)
Waveform
Mains mode: pure sine wave Battery mode: simulated sine wave
Transfer time
Typical 2 - 7 ms, 10 ms max.
DC voltage
24 V
Configuration
12 V / 9 Ah x 2
Recharge time
6 - 8 h
USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows?7 / 8 / 10
Protections
Short circuit - battery overcharge - overdischarge - overload - surge
Humidity
20 - 90% RH @ 0- 40 (non-condensing)
Noise level
<= 40 dB (1 m)
Metal Case
Net / Gross weight (kg) 12.9 / 13.3, Dimensions 25 x 380 x 225, Packaged dimensions: 161 x 369 x 290, Quantity /20ft 1000 pcs

Limited items
Code
0.502.475
Category
Tescom UPS
Voltage
110/120 VAC or 220/230/240 VAC
Voltage Range
81-145 VAC / 162-290 VAC
Frequency Range
60/50 Hz (auto sensing)
Power Factor
0,6
Voltage
110/120 VAC or 220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
+- 10
Frequency Range
60 Hz or 50 Hz ±1 Hz
Waveform
Simulated Sinewave
Transfer time
Typical 2 -6ms
Outlets
4 x Schuko
Battery Type & Number
12 V/9 Ah x 2
Typical Recharge Time
4-6 hours recover to 90% capacity
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every second
Overload
Sounding every 0.5 second
Fault
Continuously sounding
Protections
Overload, discharge, and overcharge protection
Dimension
2320 x 130 x 182
Net Weight
11 kg
Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 40dB
Optional USB / RS232 Port
Supports: Windows? 2000/XP/Vista/7/8/10, Linux, Unix, Mac OS

Available
Code
0.502.040
Category
Tescom UPS
Rated voltage
208 V / 220 V / 230 V / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load ), 176 - 280 Vac (no derating), 280 - 300 Vac (derating 50%)
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
25% +15% (settable)Total Harmonic Distortion (THDi) <= 6%
Voltage
208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Waveform
Sinusoidal
Crest factor
<= 2% (linear load); <= 5% (non-linear load)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Overload capability
105% - 125%: transfer to bypass in 1 min, 125% - 150%: transfer to bypass in 30 s, > 150%: transfer to bypass in 300 ms
Mains mode
>= 90%
Battery mode
>= 85%
ECO mode
>= 95%
DC voltage
24 V
Inbuilt battery
2 x12v 9Ah
Charging current (max.)
1A
Recharge time
8 h
TYPE
VRLA sealed lead acid maintenance free
ALARMS
On Utility failure / Low battery / Overload / UPS fault
RS232 (standard) / USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows? 7 / 8 / 10
SNMP (optional)
Power management from SNMP manager and web browser
Output Power Plugs
2 Schuko (3 IEC optional)
Operating temperature
0 - 40
Storage temperature
from -40 to 70 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000m, derating 1% for each additional 100m
IP rating
IP20
Noise level
<= 50 dB (1m)
Dimensions
144x336x214
Packaged dimensions
232x417x318
Net weight (kg)
9.5

Limited items
Code
0.081.028
Category
Batteries
Type
N/A
Form Factor
Tower
Power Output Connectors
N/A
Power Capacity
N/A
Interface
 N/A
Run Time (Up To)
N/A
Dimensions
170 x 439 x 216 mm
Weight
31.36 KG

Is expected
Code
0.502.043
Category
Tescom UPS
Rated voltage
208 V / 220 V / 230 V / 240 Vac
Voltage range
"110 -176 Vac (linear derating between 50% and 100% load), 176 - 280 Vac (no derating), 280 - 300 Vac (derating50%)"
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
- 25% + 15% settableTotal Harmonic Distortion (THDi) <= 6%
Voltage
208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Frequency
45 - 55 Hz or 55 - 65 Hz (synchronized range); 50 / 60 Hz + - 0.1 Hz (battery mode)
Waveform
Sinusoidal
Power factor
0.9
Total harmonic distortion (THDv)
<= 2% (linear load), <= 5% (non-linear load
Crest factor
3:1
Overload
105% - 125% for 1 min, 125% - 150% for 30 s, > 150% for 300 ms
DC voltage
24 V (S)
Inbuilt battery
2 x 9 A
Charging current (max.)
1A
Recharge time
Standard model: 90% capacity restored in 4 hours, Long time model: depend on the capacity of battery
Efficiency
>= 90% (Mains mode), >= 85% (Battery mode), >= 95% (ECO mode)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Protections
Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Display
LCD + LED
Standards
EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 50 Db
Dimensions
440 x 338 x 88
Packaged dimensions
545 x 428 x 194
Net weight (kg)
10.6
Gross weight (kg)
11.3

Limited items
Code
0.500.572
Category
Battery Pack
Type
N/A
Form Factor
Tower
Power Output Connectors
N/A
Power Capacity
18000 mAh
Interface
 N/A
Run Time (Up To)
N/A
Dimensions
30.1 x 11.2 x 38.2 CM
Weight
14.57KG

Limited items
Code
0.502.041
Category
Tescom UPS
Rated voltage
208 V / 220 V / 230 V / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load ), 176 - 280 Vac (no derating), 280 - 300 Vac (derating 50%)
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
25% +15% (settable)Total Harmonic Distortion (THDi) <= 6%
Voltage
208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Waveform
Sinusoidal
Crest factor
3:01
Harmonic distortion
<= 2% (linear load); <= 5% (non-linear load)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Overload capability
105% - 125%: transfer to bypass in 1 min, 125% - 150%: transfer to bypass in 30 s, > 150%: transfer to bypass in 300 ms
Mains mode
>= 91%
Battery mode
>= 86%
ECO mode
>= 96%
DC voltage
48 V
Inbuilt battery
4 x 12v 9Ah
Charging current (max.)
1A
Recharge time
8 h
TYPE
VRLA sealed lead acid maintenance free
ALARMS
On Utility failure / Low battery / Overload / UPS fault
RS232 (standard) / USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows? 7 / 8 / 10
SNMP (optional)
Power management from SNMP manager and web browser
Output Power Plugs
3 Schuko (3 IEC optional)
Operating temperature
0 - 40°C
Storage temperature
from -40 to 70 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000m, derating 1% for each additional 100m
IP rating
IP20
Noise level
<= 50 dB (1m)
Dimensions
191x418x335
Packaged dimensions
318x533x471
Net weight (kg)
18

Available
Code
0.502.042
Category
Tescom UPS
Rated voltage
208 V / 220 V / 230 V / 240 Vac
Voltage range
110 - 176 Vac (linear derating between 50% and 100% load ), 176 - 280 Vac (no derating), 280 - 300 Vac (derating 50%)
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
25% +15% (settable)Total Harmonic Distortion (THDi) <= 6%
Voltage
208 V / 220 V / 230 V / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Frequency
45- 55 Hz or 55 - 65 Hz (synchronized range), 50 / 60 Hz + - 0.1 Hz (battery mode)
Waveform
Sinusoida
Crest factor
3:01
Harmonic distortion
<= 2% (linear load); <= 5% (non-linear load)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Overload capability
105% - 125%: transfer to bypass in 1 min, 125% - 150%: transfer to bypass in 30 s, > 150%: transfer to bypass in 300 ms
Mains mode
>= 92%
Battery mode
>= 87%
ECO mode
>= 97%
DC voltage
72 V
Inbuilt battery
6 x 12v 9Ah
Charging current (max.)
1A
Recharge time
8 h
TYPE
VRLA sealed lead acid maintenance free
ALARMS
On Utility failure / Low battery / Overload / UPS fault
RS232 (standard) / USB (optional)
Supports Windows? 98 / 2000 / 2003 / XP / Vista / 2008 / Windows? 7 / 8 / 10
SNMP (optional)
Power management from SNMP manager and web browser
Output Power Plugs
4 Schuko (6 IEC optional)
Operating temperature
0 - 40°C
Storage temperature
from -40 to 70 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000m, derating 1% for each additional 100m
IP rating
IP20
Noise level
<= 50 dB (1m)
Dimensions
191x464x335
Packaged dimensions
320x573x471
Net weight (kg)
32

Available
Code
0.502.044
Category
Tescom UPS
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
"110 -176 Vac (linear derating between 50% and 100% load), 176 - 280 Vac (no derating), 280 - 300 Vac (derating50%)"
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
- 25% + 15% settableTotal Harmonic Distortion (THDi) <= 6%
Voltage
208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Frequency
45 - 55 Hz or 55 - 65 Hz (synchronized range); 50 / 60 Hz + - 0.1 Hz (battery mode)
Waveform
Sinusoidal
Power factor
0.9
Total harmonic distortion (THDv)
<= 2% (linear load), <= 5% (non-linear load
Crest factor
3:1
Overload
105% - 125% for 1 min, 125% - 150% for 30 s, > 150% for 300 ms
DC voltage
48 V (S)
Inbuilt battery
4 x 9 Ah
Charging current (max.)
1A
Recharge time
Standard model: 90% capacity restored in 4 hours, Long time model: depend on the capacity of battery
Efficiency
>= 90% (Mains mode), >= 85% (Battery mode), >= 95% (ECO mode)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Protections
Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Display
LCD + LED
Standards
"EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1"
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 50 Db
Dimensions
440 x 430 x 88
Packaged dimensions
545 x 560 x 201
Net weight (kg)
18.7
Gross weight (kg)
21.8

Limited items
Code
0.502.045
Category
Tescom UPS
Rated voltage
208 / 220 / 230 / 240 Vac
Voltage range
"110 -176 Vac (linear derating between 50% and 100% load), 176 - 280 Vac (no derating), 280 - 300 Vac (derating50%)"
Frequency
40 - 70 Hz (auto-sense)
Power factor
>= 0.99
Bypass voltage range
- 25% + 15% settableTotal Harmonic Distortion (THDi) <= 6%
Voltage
208 / 220 / 230 / 240 Vac (settable via LCD)
Voltage regulation
1 +-
Frequency
45 - 55 Hz or 55 - 65 Hz (synchronized range); 50 / 60 Hz + - 0.1 Hz (battery mode)
Waveform
Sinusoidal
Power factor
0.9
Total harmonic distortion (THDv)
<= 2% (linear load), <= 5% (non-linear load
Crest factor
3:1
Overload
105% - 125% for 1 min, 125% - 150% for 30 s, > 150% for 300 ms
DC voltage
72 V (S)
Inbuilt battery
6 x 9 Ah
Charging current (max.)
1A
Recharge time
Standard model: 90% capacity restored in 4 hours, Long time model: depend on the capacity of battery
Efficiency
>= 92% (Mains mode), >= 87% (Battery mode), >= 97% (ECO mode)
Transfer time
Mains mode to battery mode: 0 ms, Inverter mode to bypass mode: 4 ms (typical)
Protections
Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection
Communications
RS232 (standard), USB / RS485 / dry contacts / SNMP (optional)
Display
LCD + LED
Standards
"EN 62040-1, EN 62040-2, EN 61000-3-2, EN 61000-3-3, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2, IEC 62040-2, IEC 62040-1"
Operating temperature
0 - 40°C
Storage temperature
from -25 to 55 °C (without batteries)
Relative Humidity
0 - 95% (non-condensing)
Altitude
<= 1000 m, derating 1% for each additional 100 m
IP rating
IP 20
Noise level at 1m
<= 50 Db
Dimensions
440 x 560 x 88
Packaged dimensions
545 x 690 x 201
Net weight (kg)
26.8
Gross weight (kg)
29.7

Limited items
Code
0.502.426
Category
Tescom UPS
Nomina voltage
110/115/120/127VAC or 208/220/230/240VAC
Voltage range
110/115/120/127VAC or 208/220/230/240VAC
Frequency
40Hz - 70Hz
Power factor
>=0.99 @ nominal voltage (100% load)
Output Voltage
110/115/120/127VAC or 208/220/230/240VAC
Voltage regulation
1 +-
Frequency (Synchronized Range)
57 - 63 Hz or 47 - 53 Hz
Frequency Range (Batt. Mode)
50 Hz +- 0.25 Hz or 60Hz +- 0.3 Hz
Waveform
Pure Sinewave
Current Crest Ratio
3:1
Harmonic Distortion
<= 3 % THD (Linear Load)
Transfer Time AC Mode to Battery Mode
0
Transfer Time Inverter to Bypass
4 ms (Typical)
AC Mode
90%
Battery Mode
88%[BATTERIES]]
Battery Type (VRLA)
12 V / 9 AH
Numbers
6
Typical Recharge Time
4 hours recover to 90% capacity
Charging current (max.)
1.0 A
Charging Voltage
82.1 VDC ±1%
Dimension
630 x 438 x 88
Net Weight (without battery) (kgs)
29.3
Humidity
20-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 50dBA @ 1 Meter
Smart RS-232/USB & Software
Supports Windows 2000/2003/ XP/ Vista/ 2008/ 7/ 8, Linux and MAC
There are 46 products
Products 1 - 24 of 46
Prices do NOT include VAT
Our Certifications
Why we Stand out
MORE
Microsoft authorized refurbisher
Microsoft surface authorized reseller
ADISA Accredited Pass
BLANCO
WEEE
ISO 27001
ISO 14001
ISO 9001
×

This site uses cookies to distinguish visitors. To accept the use of cookies, please select
Cookies policy